ACI 318 Class B Lap Splice

When two reinforcing bars in concrete are joined by overlapping them, the overlap has to be long enough for the concrete to pass the full force from one bar to the other. ACI 318, the U.S. building code for structural concrete, calls the most common case a Class B tension lap splice. This article explains what it is, when it applies and how its length is calculated.

Concrete only — not concrete block walls

Everything below applies to reinforced concrete: footings, slabs, cast-in-place walls. Reinforced concrete masonry — a block wall with grouted cells and steel — is governed by a different standard, TMS 402, which the International Building Code points to for masonry. Its splice rules use different formulas and limits, so the numbers on this page must not be used for a block wall.

What a lap splice is

Rebar comes in stock lengths, so long runs of steel are made by overlapping one bar with the next. The bars do not touch each other structurally; the force in one bar is passed into the surrounding concrete through the bar's deformations and then picked up by the other bar. The overlap length needed to do that depends on how much force the bar can carry and how well the concrete grips it.

ACI 318 starts from the development length, written ℓd: the embedded length a straight bar in tension needs to reach its full yield strength. A tension lap splice is then a multiple of ℓd.

When a Class B splice is used

ACI 318-19 recognises two classes of tension lap splice. The shorter Class A splice is allowed only when two conditions are both met over the length of the splice: the steel provided is at least twice what the design requires there, and no more than half of the bars are spliced within the lap length. Every other case is Class B. In practice that makes Class B the default, and many engineers simply detail every tension lap as Class B.

How the length is worked out

A Class A splice is 1.0 times ℓd and a Class B splice is 1.3 times ℓd, and neither may be shorter than 12 in. So the work is in finding ℓd.

For the common case of bars with clear spacing of at least two bar diameters and clear cover of at least one bar diameter, the code offers a simplified expression: ℓd equals the bar's yield strength times the modification factors, divided by a constant times the square root of the concrete strength, times the bar diameter. The constant is 20 for No. 7 bars and larger and 25 for No. 6 bars and smaller. The square root of the concrete strength is capped at 100 psi in this calculation, and ℓd itself is never taken as less than 12 in.

  • Casting position: 1.3 when more than 12 in. of fresh concrete is placed below the bar (a top bar), otherwise 1.0.
  • Coating: 1.5 for epoxy-coated bars with small cover or spacing, 1.2 for other epoxy-coated bars, 1.0 for uncoated or galvanized bars. The casting and coating factors multiplied together need not exceed 1.7.
  • Steel grade: 1.0 for Grade 40 and Grade 60, 1.15 for Grade 80, 1.3 for Grade 100. This factor is new in the 2019 edition.
  • Lightweight concrete: the denominator is multiplied by 0.75 for lightweight concrete and 1.0 for normalweight concrete.

Worked example

Take uncoated No. 7 bars, Grade 60 (60,000 psi), at the bottom of a normalweight concrete footing with a specified strength of 4,000 psi, with spacing and cover that meet the simplified-method conditions. A No. 7 bar is 0.875 in. in diameter, and every modification factor is 1.0.

Development length: 60,000 ÷ (20 × √4,000) × 0.875 = 60,000 ÷ (20 × 63.25) × 0.875 ≈ 41.5 in.

Class B lap splice: 1.3 × 41.5 ≈ 54.0 in., well above the 12 in. minimum. Detailers usually round up to a convenient length, here 54 in.

If the same bars were top bars with more than 12 in. of concrete placed below them, the casting factor of 1.3 would raise ℓd to about 54 in. and the splice to about 70 in. — which is why splice length depends on where the bar sits, not just its size.

Which edition applies

Both the 2021 and the 2024 International Building Code reference ACI 318-19. A newer edition, ACI 318-25, was published in 2025; the published summaries of its changes to reinforcement do not list the straight-bar development length or tension lap splices, but check the edition your jurisdiction has adopted. The simplified method shown here also has a more detailed alternative that can give shorter lengths when cover and confining steel are generous.

Use with care

This page explains the provisions in our own words for understanding and estimating. It is not the code text and not a design. Splice lengths on a real project are set by the engineer of record on the drawings — follow those.